These are entry level fire alarms and are often the natural choice for smaller premises or where budget constraints exist.
Twin Wire Fire Alarm Systems
Similar to conventional fire alarm systems, though their main advantage is that sounders can be put on the detection circuit and less wiring is required.
Addressable Fire Alarm
These fire alarm systems are more flexible, intelligent and offer more control. They are therefore the natural choice for larger premises and for those with more complex system requirements.
Wireless fire Alarms
These are also known as radio fire alarms. They are the same as standard analogue addressable fire alarms, but with the advantage of no wires to interlink the detection & sounders, these are wire free fire alarms.
Fire Alarm Maintenance and Testing
Periodic fire alarm maintenance is essential to ensure that the system is in full working order and is a British Standards requirement. We provide a nationwide, reliable and cost effective fire alarm inspection, testing and certification programme to suit your requirements.
Six Monthly Test
Inspecting and completing log book
Checking false alarm records
Battery checking and testing
Checking and testing of control panel functions
Testing of fire alarm devices
Checking automatic transmission of alarm signals to an alarm receiving centre
Checking and testing of all fault indicators and circuits
Other checks and tests recommended by the manufacturer
Reporting of outstanding defects
Issuing servicing certificate
Yearly Test
Testing of the switch mechanism of every manual call point
Examining and testing of every automatic fire detector
Visual and audible testing of all fire alarm devices
Replacement of filament lamps
Checking of radio fire detection and fire alarm system signal strengths
Visual inspection of readily accessible cable fixings
Checking of the cause and effect programme
Checking of the standby power supply capacity
Reporting of outstanding defects
Issuing the servicing certificate
We can also carry out your routine testing requirements or supply easy to follow log books so a member of your staff can quickly and easily do these required interim checks. In addition, we offer a risk assessment service to help employers fulfil their statutory obligations under The Regulatory Reform Order.
Our fully trained fire alarm engineers are happy to undertake a fire alarm maintenance contract for all fire alarm systems regardless of who supplied or installed them. We can agree a schedule that meets your requirements and budget and ensure the fire alarm systems meets the necessary legal requirements.
All service contracts have access to our 24 call out facility, should you need any advice or attention to the systems we are just a phone call away. Our aim is to be on site within 4 hours of receiving a call out.
All our fire alarm engineers are fully qualified to the latest standards and they are also trained to take pride in the job they do and always put the client first.